Home Ventilation Rate Calculator

Work out the whole-house mechanical ventilation your home needs under ASHRAE 62.2, the fan size for intermittent running, and the kitchen and bathroom exhaust that goes with it.

How to use this calculator

  1. 1Enter the conditioned floor area and the number of bedrooms — those two inputs alone determine the ASHRAE 62.2 requirement.
  2. 2Choose your system type. Balanced heat recovery costs the most and is the only option that does not push or pull air through the building envelope.
  3. 3Pick a runtime. Continuous is usually both quieter and cheaper than a large fan cycling, because fan power rises steeply with airflow.
  4. 4Only take the leakage credit if you have a measured blower-door result. Guessing at ACH50 defeats the point of the credit.
  5. 5Add the kitchen and bathroom exhaust separately — local exhaust is a requirement on top of the whole-house rate, not part of it.

How the calculation works

Qtot (cfm) = 0.03 x floor area + 7.5 x (bedrooms + 1) Qmechanical = Qtot − infiltration credit Fan capacity = Qmechanical ÷ fractional runtime Air changes per hour = Qmechanical x 60 ÷ (floor area x ceiling height) Ventilation heating load (BTU/hr) = 1.08 x cfm x ΔT x (1 − recovery efficiency)
0.03 cfm/sq ft
The floor-area term — pollutants emitted continuously by materials, finishes and furnishings, whether anyone is home or not
7.5 cfm per bedroom+1
The occupancy term. Bedrooms plus one is a standardised proxy for how many people live there
ACH50
Air changes per hour at 50 pascals of pressure difference, measured with a blower door — the standard measure of envelope leakage
1.08
The sensible-heat shorthand: air’s density times its specific heat times 60 minutes, so BTU/hr = 1.08 x cfm x °F

The two terms answer different questions and neither substitutes for the other. A large house with one occupant still needs the floor-area rate, because the building itself is emitting; a small apartment with five people still needs the occupancy rate.

Intermittent fans are oversized by the reciprocal of their runtime here. That is the conservative reading — ASHRAE 62.2 Appendix C provides relative-exposure factors that are somewhat more forgiving for fans that cycle frequently, on the reasoning that short gaps do not let concentrations build fully.

The infiltration credit uses the long-standing rule of thumb that natural air change is roughly ACH50 divided by 17 to 20 for a typical house. The standard itself applies a weather- and height-corrected calculation; this is the simplification, it is applied at half value to stay conservative, and it should never be used without a real blower-door test.

Worked example

A 2,000 sq ft, three-bedroom house with a continuously running HRV

  1. 1.Floor-area term: 0.03 x 2,000 = 60 cfm.
  2. 2.Occupancy term: 7.5 x (3 bedrooms + 1) = 30 cfm.
  3. 3.Total: 60 + 30 = 90 cfm, delivered continuously.
  4. 4.House volume: 2,000 x 8 = 16,000 cubic feet, so 90 cfm is 90 x 60 ÷ 16,000 = 0.338 air changes an hour.
  5. 5.Ventilation heating load at a 40°F difference: 1.08 x 90 x 40 = 3,888 BTU/hr.
  6. 6.With 75% heat recovery that drops to 972 BTU/hr — the HRV is saving nearly 3,000 BTU/hr of heating.

Result: 90 cfm continuous

Why tight houses need mechanical ventilation

For most of the history of house building, ventilation was accidental. Air leaked in around window frames, through unsealed floorboards, down chimneys and through the gaps where the building met itself, and the resulting air change was enough — wastefully so — to keep indoor pollutants diluted. Nobody designed it; it happened because the buildings were loose.

Energy codes changed that. A house built to a modern envelope standard leaks a small fraction of what a 1950s house did, which is exactly the point: air that leaks out in January is air you paid to heat. But the pollutants did not go away. Cooking, cleaning products, off-gassing from furniture and finishes, moisture from showers and breathing, radon from the ground, and carbon dioxide from the occupants all still accumulate — and now nothing is diluting them.

That is the trade the standard exists to manage. ASHRAE 62.2 is the American residential answer: build tight, then ventilate deliberately, at a known rate, through a path you chose rather than one the building happened to have. The slogan in the building-science world — "build tight, ventilate right" — is glib but exactly correct, and the failure mode it warns against is a house sealed to a high standard with no ventilation strategy at all.

What the two terms in the formula are actually for

The requirement is 0.03 cfm per square foot of floor area plus 7.5 cfm per bedroom-plus-one, and the split is not arbitrary.

The floor-area term addresses the building. Paint, adhesives, engineered wood, carpet, upholstery and cabinetry emit volatile organic compounds continuously, at a rate roughly proportional to how much of them there is — which scales with area. A large empty house still needs ventilation.

The occupancy term addresses the people. Carbon dioxide, water vapour, and the various compounds collectively called bioeffluents are produced per person, not per square foot. The standard uses bedrooms plus one rather than an actual headcount because occupancy changes over a building’s life and cannot be inspected at design stage, while the number of sleeping rooms is fixed and countable. A three-bedroom house is assumed to hold four people whether it currently does or not.

Local exhaust sits on top of both, and is separate for a good reason: kitchens and bathrooms generate their pollutants and moisture in concentrated bursts at a known location, and capturing them at source is far more effective than diluting them across the whole house afterwards.

Exhaust, supply or balanced

The three strategies differ in what they do to the pressure inside the house, and that difference matters more than it sounds.

  • Exhaust onlya quiet fan running continuously, usually in a bathroom. Cheapest to install and the most common approach in retrofits. It puts the house at slight negative pressure, so make-up air is pulled in through whatever gaps exist — which may mean a damp crawlspace, an attached garage, or a chimney. In a house with atmospherically vented combustion appliances, that last possibility is a genuine safety concern.
  • Supply onlyfiltered outdoor air ducted into the furnace return. The house sits at slight positive pressure, so leakage flows outward and incoming air can be filtered before it arrives. The risk runs the other way: in a cold climate, pushing warm humid indoor air into wall cavities can condense moisture inside the assembly.
  • Balanced without recoveryequal supply and exhaust fans, so the house stays at neutral pressure and neither failure mode applies. Costs more than either single-fan approach and recovers no energy.
  • Balanced with recovery (HRV or ERV)the same balanced airflow, but the two streams pass through a core that transfers heat from the outgoing air to the incoming air, recovering 60–85% of it. An ERV also transfers some moisture, which helps in humid summers and in very dry winters. The most expensive option and the only one that both maintains neutral pressure and substantially reduces the energy penalty of ventilating.

The energy cost of fresh air, and when recovery pays

Ventilation is not free. Every cubic foot of outdoor air brought inside has to be heated or cooled to indoor conditions, and the shorthand for that load is 1.08 times the airflow in cfm times the temperature difference in Fahrenheit, giving BTU per hour.

For the 90 cfm example above, on a 20°F day with the house at 70°F, that is 1.08 × 90 × 50, or about 4,860 BTU/hr — a continuous load roughly equivalent to leaving a small space heater running all winter. Over a heating season in a cold climate it is a meaningful fraction of the heating bill.

This is what makes heat recovery worth its cost, and also what makes it not worth its cost everywhere. In climate zones 5 and above, where that temperature difference persists for months, an HRV recovering 75% pays back its premium over a simple exhaust fan in a reasonable number of years. In climate zones 1 through 3, where the difference is small for most of the year, the same unit may never recover its cost, and a well-controlled exhaust fan is the sensible engineering answer.

The mistakes that make a compliant system useless

Meeting the number on paper and delivering the air are different achievements, and the gap between them is wide in practice.

  1. 1Rating the fan instead of measuring the flowa fan rated at 110 cfm delivers that at a specific static pressure on a test bench. Through real ducting with elbows, a long run and a termination grille, it may deliver half. The only trustworthy figure is a measured one at the grille.
  2. 2Flex duct, crushed or coiledthe single most common reason a ventilation system underperforms. Flexible duct has several times the resistance of smooth metal at the same diameter, and a sagging or kinked run can strangle a system entirely.
  3. 3Noisethe reason continuously running fans get switched off. A fan above about 1 sone is audible enough to annoy, and an annoyed occupant will find the switch. Specifying a quiet fan is not a luxury; it is what makes the system actually run.
  4. 4No make-up air for big exhausta 600 cfm range hood in a tight house has to pull that air from somewhere. Without a dedicated make-up path it will depressurise the building, and in the worst case backdraft a water heater or fireplace.
  5. 5Ventilating from a bad sourcean intake sited next to a driveway, a dryer vent or a garage door brings in exactly what you were trying to dilute. Where the outdoor air is drawn from is as much a design decision as how much of it there is.

What this assumes, and where it stops

Assumptions

  • The ASHRAE 62.2 total ventilation rate is 0.03 cfm per square foot of conditioned floor area plus 7.5 cfm per bedroom-plus-one.
  • Intermittent fans are sized as the continuous rate divided by fractional runtime, which is the conservative approach.
  • Any infiltration credit uses a simplified ACH50 divisor and is applied at half value. It requires a measured blower-door result to mean anything.
  • The ventilation heating load is calculated at a fixed 40°F indoor-outdoor difference using the standard 1.08 sensible-heat shorthand.
  • Heat recovery efficiency is the sensible efficiency from the unit datasheet, applied as a flat multiplier.

Limitations

  • This is a design-rate calculation, not a compliance certificate. Jurisdictions adopt different editions of ASHRAE 62.2 and amend them, and some require third-party verification of measured airflow.
  • Rated fan capacity is not delivered capacity. Duct length, diameter, material, elbows and the termination all reduce it, often by a large margin, and only a measurement at the grille settles it.
  • The infiltration credit here is a simplification of a calculation the standard performs with weather and building-height corrections. Treat it as indicative.
  • Nothing here addresses combustion safety. A house with atmospherically vented appliances and an exhaust-only strategy needs a worst-case depressurisation test, which is a job for a qualified technician.
  • Latent load is not modelled. In a humid climate the moisture brought in with ventilation air can matter more than the temperature, which is the case for an ERV over an HRV.

Common questions

How much ventilation does my house need under ASHRAE 62.2?

Take 0.03 cfm for every square foot of conditioned floor area and add 7.5 cfm for each bedroom plus one. A 2,000 square foot, three-bedroom house needs 60 plus 30, or 90 cfm, delivered continuously. Kitchen and bathroom exhaust are additional requirements on top of that figure, not part of it.

Why does the formula count bedrooms instead of people?

Because occupancy changes and bedrooms do not. A designer cannot know how many people will live in a house over its life, and an inspector cannot verify a headcount at handover. Counting sleeping rooms and adding one gives a stable, checkable proxy — a three-bedroom house is assumed to hold four people whether it currently does or not.

What is the difference between an HRV and an ERV?

Both are balanced systems that pass incoming and outgoing air through a core to recover energy. An HRV transfers sensible heat only. An ERV also transfers a portion of the moisture, which helps keep humid outdoor air from loading the air conditioner in summer and keeps indoor air from becoming too dry in a cold winter. ERVs are generally preferred in humid climates and in very cold ones.

Can I just run a bathroom fan continuously instead?

Yes, and it is a legitimate ASHRAE 62.2 strategy — exhaust-only ventilation with a quiet, continuously running fan is the most common retrofit approach. The caveats are that it depressurises the house slightly, so make-up air arrives through whatever gaps exist, and that it recovers no energy. In a house with atmospherically vented combustion appliances, get a depressurisation test first.

Does a fan that runs half the time need to be twice as big?

Roughly, and this calculator assumes so. Pollutant concentration does not fall in proportion to runtime, so intermittent operation needs a proportionally larger fan to deliver the same exposure. ASHRAE 62.2 provides relative-exposure factors that are a little more forgiving for fans cycling frequently within an hour, so the reciprocal used here is the conservative end.

Sources

Formula and content last reviewed on .

Results are estimates for information only, not professional advice.

Report an error

Tools people commonly use alongside the home ventilation rate calculator.

See all science & engineering calculators →