DC Wire Gauge Calculator
Size low-voltage DC wire for 12, 24 or 48 volt systems against both voltage drop and ampacity, and see which of the two is actually limiting your run.
How to use this calculator
- 1Measure the run along the route the cable will actually take, not point to point. Cables follow chassis rails and go around obstacles, and the difference is often substantial.
- 2Enter one-way length. The calculator doubles it for the return conductor.
- 3Pick the circuit type to set a sensible drop target, or set your own. Charging circuits and inverter feeds want 2 to 3%; LED lighting tolerates 10%.
- 4Check which constraint bound the answer. If it is voltage drop, shortening the run or relocating the source will let you use thinner wire; if it is ampacity, it will not.
- 5Fuse at the source end, sized to protect the wire.
How the calculation works
Voltage drop = 2 x K x one-way length x amps ÷ circular mils
Drop percentage = voltage drop ÷ system voltage x 100
Power lost = voltage drop x amps
Required gauge = smallest that satisfies BOTH ampacity ≥ amps AND drop ≤ allowed- 2
- Current flows out on one conductor and back on the other, so the resistive path is twice the one-way distance. The most commonly omitted term in DC wire sizing
- K
- Resistivity in ohm-circular-mils per foot: 12.9 for copper at 75°C, 21.2 for aluminium
- Circular mils
- Cross-sectional area of the conductor. 10 AWG is 10,380 cmil; 4/0 is 211,600
- Ampacity
- Current the conductor can carry without its insulation overheating — a safety limit, independent of length
Low-voltage DC is sized by percentage drop, not absolute drop, and that is what makes it so different from household AC. Half a volt lost is 0.4% on a 120 V circuit and 4.2% on a 12 V one. The same wire that would be generous in a house is badly undersized in a van.
Both constraints must be met and they bind in different situations. A short battery-to-inverter cable at 250 A is ampacity-limited: it needs 4/0 whatever its length. A 40-foot run to a rear fridge at 6 A is drop-limited: the wire is thermally fine at 16 AWG and needs 10 AWG to keep the fridge running properly.
Motors make voltage drop worse than it looks. A motor at reduced voltage draws more current to deliver the same mechanical power, which increases the drop further — a feedback loop that ends in a hot cable and a stalled pump.
Worked example
A 30 A DC circuit over a 15 ft run on a 12 V system
- 1.Allowed drop: 3% of 12 V = 0.36 V.
- 2.Try 10 AWG (10,380 cmil): 2 x 12.9 x 15 x 30 ÷ 10,380 = 11,610 ÷ 10,380 = 1.119 V — 9.3%, far too much.
- 3.Try 6 AWG (26,240 cmil): 11,610 ÷ 26,240 = 0.442 V — 3.7%, still over.
- 4.Try 4 AWG (41,740 cmil): 11,610 ÷ 41,740 = 0.278 V — 2.3%, inside the target.
- 5.Ampacity check: 4 AWG is rated 95 A in free air, comfortably above 30 A.
- 6.So 4 AWG, limited by voltage drop rather than ampacity — the wire is thermally fine at 10 AWG and it is the length that forces it up.
- 7.The load sees 11.72 V, and 8.3 W is lost as heat in the cable.
Result: 4 AWG copper
Why 12 volts needs such fat wire
Anyone coming to DC wiring from household electrics finds the wire sizes absurd. A 30 amp circuit in a house runs on 10 AWG; the same 30 amps over a modest run in a 12 volt system wants 4 AWG, a conductor four times the cross-section. The reason is not that DC is different in kind — it is that the tolerance is different by a factor of ten.
Voltage drop is judged as a percentage of the supply. Half a volt lost in a 120 volt circuit is 0.4%, invisible. The same half volt in a 12 volt circuit is 4.2%, which is at the edge of acceptable and, on a charging circuit, is money.
The current is higher too, for the same reason. Delivering 400 watts at 120 volts takes 3.3 amps; at 12 volts it takes 33. Drop is proportional to current, so the twelve-volt circuit suffers ten times the drop before the percentage tolerance is even considered. Combined, the two effects mean a low-voltage circuit is roughly a hundred times less tolerant of a given length of a given wire.
This is the single strongest argument for 24 or 48 volt systems in anything above modest power. Doubling the system voltage halves the current and doubles the volts available to lose, so the wire needed falls by roughly a factor of four.
The two constraints, and which one binds
Every conductor has to pass two independent tests, and they are about different failure modes.
Ampacity is a safety limit. Current heats a conductor, and enough heat degrades the insulation, softens terminations and eventually starts a fire. The ampacity of a wire depends on its cross-section, its insulation temperature rating, and how easily it can shed heat — which is why the same wire is rated lower in conduit, in a bundle, or in a hot engine bay than it is hanging in free air. Ampacity does not depend on length at all.
Voltage drop is a performance limit. It does not endanger anything; it simply means the load does not get the voltage it expected. Drop is proportional to length, so it is the constraint that grows with distance.
Which one binds tells you what to do about it. A battery-to-inverter cable carrying 250 amps over four feet is ampacity-limited: it needs 4/0 regardless of how short you make it, and relocating the inverter saves nothing. A 40-foot run to a rear-mounted fridge drawing 6 amps is drop-limited: 16 AWG would carry it safely all day, but the fridge would see 10 volts, so it needs 10 AWG — and moving the source closer would let you go back down.
What voltage drop actually costs
The consequences differ by circuit type, which is why the target percentage differs too.
- On a charging circuit — the loss is direct. Every volt dropped between a solar array and a battery is energy the panels generated and the battery never received, forever. A 3% loss on a system that cost real money to install is worth the heavier cable.
- On an inverter feed — the loss is a shutdown. Inverters monitor their DC input and cut out at a low-voltage threshold to protect the battery. A sagging cable makes the inverter see a flat battery when the battery is fine, and the fault appears as an inverter that trips whenever the kettle goes on.
- On a motor circuit — the loss compounds. A motor at reduced voltage draws more current to deliver the same mechanical output, which increases the drop, which reduces the voltage further. Pumps run slow, fans move less air, and the cable runs hot.
- On LED lighting — the loss is mostly invisible. LED drivers regulate across a wide input range, and a 10% drop typically produces no perceptible dimming — which is why the 10% allowance for lighting is genuinely reasonable rather than a corner cut.
Fusing, and the thing that actually catches fire
Wire sizing and overcurrent protection are two halves of the same job, and the relationship between them is frequently misunderstood: the fuse protects the wire, not the appliance.
The appliance has its own protection, or it does not and that is its manufacturer’s problem. What the fuse in your system exists to prevent is a conductor carrying more current than it can shed as heat — a short circuit, a chafed cable against a chassis, a terminal that has worked loose and is arcing. A battery bank can deliver thousands of amps into a dead short, and a cable in that condition becomes a heating element in seconds.
Two rules follow. The fuse is sized to the wire’s ampacity, not the load’s rating — a wire rated 95 amps feeding a 30 amp load should be fused somewhere between the two, closer to the load, but never above what the wire can carry. And the fuse goes at the source end, within inches of the battery positive terminal, because a short anywhere along the cable bypasses a fuse fitted at the far end entirely.
For the main battery cable specifically, an ordinary blade or glass fuse is not adequate. Their interrupt rating — the current they can break without arcing across the gap — is far below what a large battery can deliver. Class T fuses, or an appropriately rated ANL, exist for this and are the correct choice on any bank capable of high short-circuit current, which includes essentially every lithium installation.
Details that catch people out
Beyond the arithmetic, several practical points regularly cause problems in DC installations.
- 1Measure the real route — cable follows chassis rails, goes around bulkheads and loops to reach a grommet. The straight-line distance between two components is frequently half the cable actually needed, and the drop is proportional to what you install rather than what you intended.
- 2Use fine-stranded cable — building wire with a few thick strands is stiff and fatigues where a vehicle vibrates. Marine-grade or welding cable with many fine strands flexes without work-hardening, and is what ABYC requires for boats for exactly this reason.
- 3Terminations matter as much as conductors — a poorly crimped lug has resistance, and resistance at a high-current joint generates heat exactly where you cannot see it. Crimp properly with the right tool, and check terminals for warmth after a heavy load — a warm lug is a warning.
- 4Tinned copper near salt — in marine and coastal use, plain copper corrodes and the corrosion creeps under the insulation. Tinned copper costs a little more and is standard practice for good reason.
- 5Do not use the chassis as a return casually — it works in a vehicle designed for it, with proper bonding. In a conversion, a chassis return through painted panels and bolted joints has unpredictable resistance and makes drop impossible to calculate. Run both conductors.
What this assumes, and where it stops
Assumptions
- Voltage drop uses the standard formula with K = 12.9 for copper and 21.2 for aluminium at 75°C.
- The run length entered is one-way; the calculation doubles it for the return conductor.
- Ampacity figures are free-air 75°C values. No derating is applied for bundling, conduit or ambient temperature.
- Current is treated as continuous at the value given. Motor starting surges are not used for sizing, which is standard practice.
- The recommended gauge must satisfy both ampacity and the drop target.
Limitations
- Ampacity in a real installation is usually lower than the free-air figure used here. Bundled conductors, conduit, insulation and engine-bay heat all reduce it, sometimes substantially.
- RV and marine installations follow their own standards. ABYC E-11 for boats is stricter than NEC on temperature ratings and requires stranded conductors.
- Terminations, connectors, switches, shunts and fuse holders all add resistance that this calculation ignores. A dozen crimps on a long run can add meaningfully to the total drop.
- The K values are for 75°C conductor temperature. A cool conductor has slightly less resistance and a hot one more, so the real drop varies with load and ambient.
- Nothing here sizes overcurrent protection beyond the general guidance in the notes. Fuse selection also depends on interrupt rating, which matters greatly on large battery banks.
Common questions
What size wire do I need for a 30 amp 12 volt circuit?
It depends entirely on length. Over 5 feet, 10 AWG is fine. Over 15 feet you need 4 AWG to stay within 3% drop, and over 30 feet you are into 1/0. Ampacity alone would allow 10 AWG at any length — it is voltage drop that forces the wire up, and it grows in direct proportion to distance.
Why do I double the length in the voltage drop formula?
Because current flows out along the positive conductor and back along the negative, so it passes through twice the one-way distance of copper. A 15-foot run means 30 feet of conductor in the circuit. Forgetting the factor of two halves the calculated drop and is the single most common mistake in DC wire sizing.
What voltage drop is acceptable in a 12V system?
Three percent for anything performance-critical — charging circuits, inverter feeds, motors and pumps. Ten percent is generally accepted for LED lighting and low-draw accessories, where a small drop produces no visible effect. On a 12 volt system, 3% is only 0.36 volts, which is why runs get expensive quickly.
Is ampacity or voltage drop the limiting factor?
Short high-current runs are ampacity-limited: a battery-to-inverter cable at 250 amps needs 4/0 however short it is. Long lower-current runs are drop-limited: a 40-foot run at 6 amps is thermally fine on 16 AWG but needs 10 AWG for the load to work properly. Knowing which tells you whether shortening the run would help.
Where should the fuse go?
At the source end, within inches of the battery positive terminal, and sized to protect the wire rather than the load. A fuse at the far end protects nothing, because a short anywhere along the cable bypasses it. For main battery cables use a Class T or properly rated ANL — ordinary blade fuses cannot safely interrupt the current a large bank can deliver.
Sources
- Small solar electric systems — wiring and components — US Department of Energy
- NFPA 70, National Electrical Code — free public access — National Fire Protection Association
- Electrical safety in recreational vehicles and standards — National Fire Protection Association
Formula and content last reviewed on .
Results are estimates for information only, not professional advice.
Related calculators
Tools people commonly use alongside the dc wire gauge calculator.